Electrostatic Hazard Tests

Test materials for electrostatic risk to prevent ignition hazards and ensure safe use in explosive atmospheres.

Electrostatic Hazard Testing measures how materials generate, hold, or discharge static electricity.

It helps classify surfaces as conductive, dissipative, or insulating, and assesses the risk of discharges in flammable environments.

Electrostatic Hazard Testing Types

Surface Resistivity Test – Solid Materials

Surface resistivity is a measure of the electrical resistance across a unit square surface of material and is a means for classifying materials as conductive, semi-conductive (static dissipative), or insulating.

Electrostatic Chargeability Test (Charging Test with Non-Conductive Materials)

Electrostatic testing plays a vital role in industries where flammable materials, powders, gases, or sensitive electronic components are handled. This process evaluates the potential of materials, equipment, or environments to generate, store, or discharge static electricity. Left unchecked, static electricity can pose serious risks, including ignition, explosions, fires, or damage to electronic components. 

One important aspect of electrostatic testing is assessing the risk of brush discharges in explosive atmospheres. The results are compared to permissible charge buildup limits outlined in international standards, defined as:

  • 60 nC for Group I or IIA equipment 
  • 30 nC for Group IIB equipment 
  • 10 nC for Group IIC equipment

Why Electrostatic Hazard Tests Matter?

Electrostatic hazard testing is essential in environments where static build-up could lead to fires, explosions, or equipment damage.

The Surface Resistivity Test helps classify materials as conductive, dissipative, or insulating, important to preventing unwanted charge accumulation on surfaces. The Electrostatic Chargeability Test assesses whether non-conductive materials can build up enough charge to cause hazardous discharges.

Together, these tests support safer material selection, help prevent ignition in explosive atmospheres and ensure compliance with international safety standards.

Contact us

Testing Methodology

The Surface Resistivity Test for solid materials is carried out in accordance with NEK EN 60079-32-2:2015, Explosive Atmospheres – Part 32-2: Electrostatic Hazards – Tests. It is used to classify materials as conductive, semi-conductive (static dissipative), or insulating.

The test involves placing two identical rectangular metal electrodes in parallel on the material’s surface, with the distance between them equal to the electrode length. A DC voltage is applied to one electrode, and the current flowing across the surface to the other is measured. Surface resistivity is then calculated using the voltage, current, and electrode geometry.

Humidity can significantly affect results, as water vapour in the air may be absorbed or adsorbed onto the material surface, increasing conductivity. For this reason, testing is typically performed under both low humidity conditions (below 10%) and at ambient humidity to reflect practical scenarios.

Meanwhile, the Electrostatic Chargeability Test is conducted according to NS‑EN ISO 80079‑36:2016, Explosive Atmospheres – Part 36. This method checks if materials can charge up and cause brush discharges—tiny sparks that may ignite gases or dust in hazardous zones. 

In practice, a conditioned sample (typically 150 × 150 mm) is rubbed or otherwise electrically charged under controlled humidity. The test uses a spherical electrode to provoke a single discharge, measuring the charge released to see if it exceeds safety limits. Results indicate whether a material is safe to use, or if grounding or conductive coatings are needed to prevent static-related ignition.

Value to Your Business

  • Carrying out surface resistivity testing helps you determine whether a material is conductive, dissipative, or insulating, and assess the risk of static build-up on equipment surfaces
  • Performing chargeability tests helps you identify materials that can accumulate static and cause brush discharges, reducing the risk of ignition in explosive atmospheres
  • Using test results helps you choose anti-static materials, surface treatments, and grounding solutions that suit your operational needs
  • Including electrostatic testing in your maintenance plan helps you detect static risks early and take action before they lead to fire, explosion, or equipment failure
  • Following recognised standards (EN 60079‑32‑2 and ISO 80079‑36) helps you demonstrate compliance during audits and satisfy regulatory or insurance requirements

Featured Insights

Explore relevant materials providing insights into our service.

Validate your project with proven test data

Work with our specialists to get insights you need for smarter decisions.



Comprehensive combustible dust testing services

  • Explosibility Screening Test (Yes/No) Read more
  • Minimum Ignition Energy (MIE) of Dust Cloud Test Read more
  • Minimum Ignition Temperature (MIT) of Dust Cloud Test Read more
  • Minimum Ignition Temperature (MIT) of Dust Layer Test Read more
  • Explosion Severity Test (Pmax, dP/dt, KST) Read more
  • Lower Explosion Limit Test (LEL, MEC) Read more
  • Limiting Oxygen Concentration (LOC) Test Read more
  • Hot Storage Test in Wire Baskets (Self-Ignition Temperature) Read more
  • UN Transportation Tests (UN Class 4) Read more